Guaranteeing the highest quality products has always been our pursuit

Emerson Fisher DLC3100 Level Transmitter controller

  • Emerson Fisher DLC3100 Level Transmitter controller
  • Emerson Fisher DLC3100 Level Transmitter controller
  • Emerson Fisher DLC3100 Level Transmitter controller
  • Emerson Fisher DLC3100 Level Transmitter controller
  • Emerson Fisher DLC3100 Level Transmitter controller
  • Emerson Fisher DLC3100 Level Transmitter controller
Emerson Fisher DLC3100 Level Transmitter controller
  • Fisher
  • Singapore
  • 30 days
  • 500 sets/month

DLC3100 and DLC3100SIS digital level controllers transmitters are HART communicating instruments that are used with level sensors to measure liquid level, level of the interface between two liquids, or liquid density.

 

  Fisher DLC3100 digital contoller Transmitter from Singapore


Fisher transmitter




DLC3100




Fisher DLC3100















Prameter of DLC3100 level controller transmitter

The DLC3100 digital level controller transmitter front cover comes with push buttons and a liquid crystal display for user setup and calibration, without the need of an external tool. The main board and terminal assemblies are potted. Its modular design allows for easy replacement. The sensor module is not field replaceable, as it requires factory calibration. There is a cover protecting the sensor module that has anti-tamper paint. This cover must not be removed at any time to ensure accuracy. 

The DLC3100 is application for replacement of DLC3010 controller transmitter.


Installation of DLC3100 level transmitter
A 249 sensor may be shipped with the DLC3100 digitallevel controller installed or they may be shipped
separately.When shipping a skid mounted system, where the displacer cannot be restrained, it is recommended that the transmitter be uncoupled and the lever assembly
locked to prevent damage. The transmitter must be re-coupled at commissioning, and a zero-trim will be required.


Ordering Information
When ordering, specify:
 Process temperature and pressure and ambient air temperature
 Application
 Liquid level service (specific gravity)
 Interface level service (specific gravity of both liquids and minimum differential gap or span required)
 Density service (minimum and maximum specific gravity required)
 Liquid(s) Category (Water/Steam, Hydrocarbon, H2SO4, Custom Fluid)
 Liquid(s) Type (Water, Saline, Saturated Water,saturated Steam, Crude Oil, Refined Product, Gas Well Condensate, H2SO4 %)


The compare for DLC3100 and DLC3010
(DLC3010 stopped production)

Feature

DLC3100 HART

DLC3100 SIS

DLC3010

Guided Setup

Yes

Yes

Yes

Calibration

Yes

Yes

Yes

Setup & Calibration Log

Yes

Yes

No

Local User Interface

Yes

Yes

No

Process Temperature Compensation

Yes (RTD/Manual)

Yes (RTD/Manual)

Yes (RTD/Manual)

Fluid Density Table

Yes

Yes

No

Burst Communication

No

No

Yes

Level Application

Yes

Yes

Yes

Interface Application

Yes

Yes

Yes

Density Application

Yes

No

Yes

Alert Event Record

Yes

Yes

No

Trip Recovery Mode

Auto

Auto/Manual

Auto

SIL 2 Capability

No

Yes

No

HART Version

5

5

5

Fisher transmitter

Certificate of original Fisher DLC3100 digital contoller Transmitter from Singapore




Packing and delivery


DLC3100



Fisher DLC3100


About us 


Fisher transmitter


DLC3100


Fisher DLC3100




Download
Get the latest price? We'll respond as soon as possible(within 12 hours)

Privacy policy

close left right